+86 132 2906 5196

AL/XLPE/SWA/PVC NA2XRY 0.6/1kV Aluminum SWA Cable

0.6/1kV NA2XRY Cable, AL/XLPE/SWA/PVC

Application:

· Power and auxiliary fixed wiring cables

· Power networks

· Underground

· Outdoor and indoor devices

 

Voltage Rating (Uo/U) : 0.6/1K 

Temperature Rating Fixed: -25°C to +90°C   

For any more information or advice please contact the office on 0086-13229065196(WhatsApp/WeChat)

Share:

Details

AL/XLPE/SWA/PVC Cable  

AL/XLPE/SWA/PVC Armoured Power Cables are the perfect choice when you need the toughest and most durable armoured cable for power distribution and transmission. Made with a layer of steel wire armoured (SWA), polyethylene (XLPE) thermosetting insulation, and hard-wearing PVC, these armoured cables can withstand twisting, crushing, impacts, temperature extremes, moisture, chemical hazards, and more. They’re suitable for use in a range of environments, from industrial and manufacturing facilities to construction  

Construction

AL/XLPE/SWA/PVC NA2XRY 0.6/1kV Aluminum SWA Cable

Description: NA2XRY, XLPE Insulated Copper Power Cable   

Conductors:Class 1 or Class 2 of plain Aluminum,or of Class 5 of plain aluminum in accordance with IEC 60228.

Insulation:Cross-linked polyethylene XLPE

Insulation Colour:Natural or as required

Filler: Non-hygroscopic Material

Inner Sheath: Polyvinyl Chloride PVC

 Reinforcement: Steel Wire
Outer Sheath:Extruded Polyvinyl Chloride PVC&Polyethylene PE&LSZH

Colour of Sheath: Black

Voltage Rating (Uo/U)600/1000V   

Test Voltage: 3.5kV for 5 minutes

Physical Properties

Maximal operating conductor Temperature: up to 70℃(PVC insulation); up to 90(XLPE insulation)

Operating Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)

Short Circuit Temperature(5 seconds maximum duration): 140-160℃(PVC insulation);250℃(XLPE insulation)

Technical Data

0.6/1kV-1 core aluminum conductor XLPE insulated steel wire armored PVC sheathed power cable
Nominal cross sectional areaInsulation thicknessNon-magnetic steel Wire diameterSheath thicknessApproximate outer diameterApprox.
weight
Max.D.C resistance of conductor(20℃)Current carrying capacity 
mm2mmmmmmmmkg/kmΩ/kmIn Air(A)In Ground(A)
1X100.70.81.813.22873.0839 53 
1X160.70.81.814.33361.9150 68 
1X250.90.81.8164171.266 88 
1X350.91.251.817.55750.86881 105 
1X5011.251.8196730.64198 123 
1X701.11.251.820.88000.443126 151 
1X951.11.61.823.110650.32154 182 
1X1201.21.61.824.712120.253182 207 
1X1501.41.61.826.613980.206210 235 
1X1851.61.61.828.816100.164245 266 
1X2401.71.61.931.318900.125290 312 
1x3001.82234.724340.1340 354 
1x400222.238.729460.0778399 403 
1x5002.222.342.935490.0605469 466 
1X6302.42.52.44845950.0469553 532 
1X8002.62.52.652.754590.0367644 613